DeviceNet Network Scanner
Instruction Sheet
Warning
This Instruction Sheet only provides descriptions for electrical specifications, general specifications, installation and
wiring.
DVPDNET-SL is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust,
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device
(e.g. key or specific tools are required for opening the enclosure) in case danger and damage on the device may
occur. Do NOT tough any terminal when the power is switched on.
Introduction
Functions:
Support Group 2 server device and Group 2 only
server device.
Support DeviceNet Master mode and Slave mode.
Support EDS file configure in ElinkConfigurator
software.
Support explicit connection via Predefined
Master/Slave Connection Set. (Explicit message)
Connection size is flexible from 1 to 390 bytes in
input and output area.
Nameplate Explanation
DNET-SL 0T62600001
MADE IN XXXXXX
Delta PLC model name
VX.XXXX
Power input specification
Barcode, series No., version
Model Name and Serial Number Explanations
Serial Number
Production series
Production week
Production year (2006)
Production plant (Taoyuan)
Serial number of version
Production Model
Product Series
For SV MCU
Model Serial Number
Model type
For SV left side extended module
26 00016T0DNET-SLDVP DNET S L
Product Profile
Unit: mm
1
Model name
2
Extension port
3
Power, MS, NS LED
4
DIN rail clip
5
Message display
6
Extension clip
7
Address switch
8
Function switch
9
DeviceNet connection port
Specifications
DeviceNet Connection
Interface
Removable connector
(5.08mm)
Transmission
method
CAN
Transmission
cable
2-wire twisted shielded cable
with 2-wire bus power cable
and drain
Electrical
isolation
500V DC
Communication
Message type
I/O polled, bit-strobe, change
of state/cyclic
Baud rates
125 Kbps; 250 Kbps;
500 Kbps
Product code
64
Product type
12
Vendor ID
799 (Delta Electronics Inc.)
Electrical Specification
Module power voltage: All other power derived from PLC controller power supply
DeviceNet
Network power input: 11 ~ 25V DC; Current: less than 50mA (25V DC)
Environment Specifications
Noise immunity
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV,
Analog & communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Environment
Operation: 0ºC ~ 55ºC (temperature); 50 ~ 95% (humidity); pollution degree 2
Storage: -40 ºC ~ 70ºC (temperature); 5 ~ 95% (humidity)
Vibration/shock
resistance
Standard: IEC1131-2IEC 68-2-6 (TEST Fc)/IEC1131-2 & IEC 68-2-27 (TEST Ea)
Approvals
Installation
Profile (Dimensions are in millimeter and [inch])
3
2
0
1
4
9
8
6
7
0
MS
NS
5
DR 0
DR 1
x10
IN 1
IN 0
DVPDNET
x10
5
3
2
4
0
1
8
6
7
9
1
Installing DVPDNET-SL With PLC MPU
DVPDNET
DVP28SV
STOP
2
2
1
Pin Definition Of DevicetNet Connection Port
Pin Signal Color Content
1 V- Black 0 VDC
2 CAN_L Blue Signal-
3 Drain - Shield
4 CAN_H White Signal+
5 V+ Red 24 VDC
1
2
3
4
5
MAC ID Setting
Switch setting Content
0…63 Valid DeviceNet MAC ID setting
Others Invalid DeviceNet MAC ID setting
9
1
6
4
5
0
0
9
1
3
2
7
8
2
5
6
4
3
7
8
Function Switch Setting
DR1 DR0 Baud rate
OFF OFF 125K bps
OFF ON 250K bps
ON OFF 500K bps
IN0
Reserved
IN1 Reserved
Connecting DVPDNET-SL Scanner With Slave Devices
Connection Example:
PORT2PORT1
DeviceNet
DVP-PS01
VFD-B
DNA02
DVPDT01
DVP-12SC
DVP28SV
DVPDNET-SL
DVPDNET
DVP28SV
RUN
STOP
RUN
STOP
D
V
P
-
1
2
S
C
D
T
0
1
L
N
0
V
Cable Length and Baud Rates
The maximum cable length in a segment depends on the transmission speed. DeviceNet communicates at
speeds from 125K bps to 500K bps over distances from 100 to 500 meters.
Baud rates (bps) 125K 250K 500K
Length (m) 500 250 100
Configuration
Access DNET Scanner With PLC
When DNET scanner is connected to PLC, it will get a data area that maps to DNET scanner in PLC.
Mapped D registers
Index of DNET
scanner
Output image table Input image table
1 D6250 – D6497 D6000 – D6247
2 D6750 – D6997 D6500 – D6747
3 D7250 – D7497 D7000 – D7247
4 D7750 – D7997 D7500 – D7747
5 D8250 – D8497 D8000 – D8247
6 D8750 – D8997 D8500 – D8747
7 D9250 – D9497 D9000 – D9247
8 D9750 – D9997 D9500 – D9747
The index of DNET scanner is the sequence number of scanner. The 1
st
scanner is near to SV MPU and the index number is1. The 2
nd
scanner is
near to the 1
st
scanner in the left side and to be numbered as 2. The others are numbered as 3, 4, …and so on.
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - Configuration

http://www.delta.com.tw/industrialautomation/ 5011649300-DLE02006-12-27 DeviceNet Network Scanner Instruction Sheet Warning  This Instruction Shee

Seite 2 - Troubleshooting

Input and Output Image Tables The mapping of the scanner input and output image (the 1st scanner): Output image Input image D register Image mapping

Kommentare zu diesen Handbüchern

Keine Kommentare