Delta-electronics RTU-DNET Bedienungsanleitung Seite 16

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 41
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 15
DeviceNet Remote I/O Communication Module RTU-DNET
DVP-PLC Application Manual
14
Attribute
ID
Access
rule
Name Range Default Explanation
61 Get/Set
Output data
length for
module 6
N/A N/A
Length of output data of special
module 6
62 Get/Set
Start CR for
module 7
output data
N/A N/A
Start CR for the output data of special
module 7
63 Get/Set
Output data
length for
module 7
N/A N/A
Length of output data of special
module 7
64 Get/Set
Start CR for
module 8
output data
N/A N/A
Start CR for the output data of special
module 8
65 Get/Set
Output data
length for
module 8
N/A N/A
Length of output data of special
module 8
Class 0x9C – Extension module parameter object
Class attribute
Attribute ID Access rule Name Data type
1 Get Revision UINT
2 Get MaxInstance UINT
Instance 1 ~ 8 (CR for the 1
st
~ 8
th
special module)
Attribute ID Access rule Name Data type
1 Get Content in CR#0 UINT
2
Get/Set
Content in CR#1 UINT
3
Get/Set
Content in CR#2 UINT
… … UINT
9
Get/Set
Content in CR#8 UINT
10
Get/Set
Content in CR#9 UINT
… … UINT
Note:
z When you modify the content in CR of the special module through DeviceNet, please read out the
content again (Get_Attribute_Single) after the modification and confirm that it has been modified
successfully.
z The content in some CRs of the special module cannot be modified. Therefore, please pay attention
to these parameters when you are modifying them.
4.3 DeviceNet I/O Mapping Data
1. Control word and status word in RTU-DNET
Control word
bit Status value Explanation
0 Setting RTU-DNET to STOP mode
0
1 Setting RTU-DNET to RUN mode
1 0/1 Reserved
Seitenansicht 15
1 2 ... 11 12 13 14 15 16 17 18 19 20 21 ... 40 41

Kommentare zu diesen Handbüchern