PROFIBUS DP Slave Communication Module DVPPF02-H2
DVP-PLC Application Manual
11
¡ Establishing PROFIBUS DP network by DVPPF02-H2 (hardware configuration)
1. Establish the network including S7-300 and DVPPF02-H2 by PROFIBUS DP bus, S7-300 as master
and DVPPF02-H2 as slave.
S7-300
PROFIBUS DPPROFIBUS DPPROFIBUS DP
DVPPF02-H2DVP-EH2DVP-EH2DVP-EH2
2. Set the address of DVPPF02-H2 to “11” (decimal). See "21.3.1 Address Switch” section for how to set
up the address.
After the address is set, re-power DVP-EH2.
3. Check and make sure S7-300, DVP-EH2 and DVPPF02-H2 all operate normally and the wiring of the
entire network is correct.
¡ Configuring DVPPF02-H2 on PROFIBUS DP (software configuration)
Establishing a new file by “Project Wizard”.
1. Open SIMATIC Manager software.
2. Select “File” => “New Project Wizard…”.