03 - Comparison of Terminals between CP2000 & VFD-F
3-3
VFD-F VFD-CP2000
Terminals
Terminal Function Factory Setting (NPN mode)
Terminals
Terminal Function Factory Setting (NPN mode)
Auxiliary analog voltage input
AVI2
Impedance: 20kΩ;
Range: 0 ~ +10VDC=0~ Max.
Output Frequency
(Pr.01-00);
AFM1 Analog frequency / current meter 1
0 to 10V correspond to Max.
operation frequency
AFM1
AFM2 Analog frequency / current meter 2
4 to 20mA correspond to 2
times of output current
AFM2
Impedance: 100Ω (current
output);
Output current: 20mA max;
Resolution: 0~10V corresponds
to Max. operation frequency;
Range: 0~10V à 0~20mA;
AFM Switch: factory setting is
0~10V;
ACM Analog control signal (common)
ACM Analog Signal Common Common for analog terminals
S1 Factory setting: short-circuit
SCM Power removal safety function for emergency stop.