Chapt er 2 Setting an HMI
2-2 9
The table below shows “Auto Picture Change” is Variation.
Example of the State Graphic
Table 2.5.5 Example of the State Graphic
Read
address
State Graphic Element
Numeric Entry Element
Numeric Entry Element
Read address
$326 Write address
$326 Write address
$327
Picture
Set the State Graphic
State 0 State 1 State 2
Properties
State Graphic Element
Data Type Data Format State Counts
Auto Picture
Change
Word
Unsigned
decimal
3 Variation
Execution
results
The read address in the state graphic element represents the register for
changing state pictures. The Read Address+1 allows users to access to
the register for setting the auto picture change as variation.
After creating the element, run “Compile” and download it to the HMI. Next,
select the numeric entry element {$327} and input a non-zero value in the
element. Then, the state graphic will automatically change and display the
selected pictures according to the defined picture change time. When selecting
the numeric entry element {$326}, users can input the corresponding state
graphic data in the element. If the numeric entry element {$327}is “0”, the state
graphic will stop the auto picture change.