Operation Interface Panels Series
TP04G-AS1
Instruction Sheet
Warning
Always read this manual thoroughly before using the TP04G.
DANGER! DC input power must be OFF before any maintenance. Do
not connect or remove wires and connectors while power up to the circuit.
Only the qualified technicians are allowed to do the maintenance.
The display panel of the TP04G is waterproof. But please keep away
grease, corrosive liquids or sharp objects from contacting the TP04G.
DANGER! The TP04G requires 24VDC input power. The 24VDC input
power should not be connected to the RS-485 communication port. The
unit may be destroyed and can’t be repaired if the input power is
incorrectly applied. Please confirm the input power wiring is correct
before power up.
DANGER! An electrical charge will remain on the DC-link capacitors for 1
minute after power has been removed. This residual power may be
hazardous and the TP04G should not be worked on until this charge has
dissipated. To prevent personal injury, do not conduct any wiring or
investigation on the TP04G until 1 minute after power off.
CAUTION! Always ground the TP04G using the grounding terminal. Not
only will this act as a safety, but help to filter out electrical noise. The
grounding method must comply with the laws of the country where the
unit is to be installed.
CAUTION! If you turn the fixed support that is packaged together with
TP04G too tight, TP04G may be damaged.
Nameplate
Production model
Power input Spec.
Barcode and
serial number
Operation Panel
MODEL :
POWER INPUT :
TP04GAS1T318002
V X.XX
TP04G-AS1
24VDC 3.5W
DELTA ELEC TRONICS , INC MAD E IN XXXXX XX
Version
Note: The words of “MADE IN XXXXX” will be different due to the
manufacturing location.
Model Explanation Serial Number Explanation
TP 04 G AS 1 -
Series name
Reserved
Reserved
T: Te x t mo d e
G: Graphic mode
LCD Spec.
TP04GAS 1 T 3 18 002
Production model
Production serial number
Production weeks
Production year (2003)
Production factory
Version
T: Taoyuan
Outline Back Panel
LCM
Display Area
RS-485 Indication LED
Escape/Exit
Shift Key
Arrow keys
Function Keys
Enter key
RS-232 Indication LED
Alarm Indication LED
RS-232
+24V
0V
+
RS-485
Battery
Cover
Extension Slot
Dimensions (Unit: mm)
Front Panel Right Side Diagram
97.00
[3.82]
147.00 [5.79]
85.00
[3.35]
Vertical View
Back Panel Mounting Panel Dimension
Thickness Range 0.5~9mm
135~136.5[5.31~5.37]
85
[3.35]
Installation Method
One easy way is insert TP04G to the opening hole of panel and tight up the
screws. However, if a firm mounting TP04G to the panel is needed, please use
the fixed support accessory which is packed together with TP04G, then infix the
fixed support in the back and tight up the screws.
If you turn the screw exceeds torque: 4-5(kg-cm), TP04G may be damaged.
Thickness:
0.5~9.0mm
Panel Function
Component Explanation
Alarm Indication
LED
Status 1: When power is on, the LED will flash slowly.
Status 2: When there is an abnormal situation, the LED will
flash quickly along with an alarm sound.
RS-232 Indication
LED (Yellow)
Will flash when transmitting program and communicating
by using RS-232.
RS-485 Indication
LED (Green)
Will flash when communicating by using RS-485.
LCM display Area Liquid Crystal Module display area.
Esc (Escape/Exit)
Used to cancel an incorrect input, or to Exit a programming
step.
Arrow Keys
UP/Pg Up: Used to increase the value or move screen one
page up.
Pg Dn/DOWN: Used to decrease the value or move screen
one page down.
Left: Left direction key. (move curser to left)
Right: Right direction key. (move cursor to right)
Shift Key Used to select keys F5, F6, F7, F8, F9.
Function Keys
F0/F5: used to be a constant 0 (F0), or 5 (Shift + F0) when
they are in system menu. User can define the functions
separately when they are in user page.
F1/F6: used to be a constant 1 (F1), or 6 (Shift + F1) when
they are in system menu. User can define the functions
separately when they are in user page.
F2/F7: used to be a constant 2 (F2), or 7 (Shift + F2) when
they are in system menu. User can define the functions
separately when they are in user page.
F3/F8: used to be a constant 3 (F3), or 8 (Shift + F3) when
they are in system menu. User can define the functions
separately when they are in user page.
F4/F9: used to be a constant 4 (F4), or 9 (Shift + F4) when
they are in system menu. User can define the functions
separately when they are in user page.
Enter key Used to input a value or accept a programming command.
Electrical Specification
TP04G-AS1
Function Key/Digital Key F0~F4, ESC, SHIFT, ENTER and ARROW keys
External Input Power 24V (3.5W Max.)
Memory Capacity 256K Byte
CPU 16 bits
RAM of System 32K Byte
Communication
Interface
Com1: RS-232 and Com2: RS-485
Waterproof Class of
Front Panel
IP65/NEMA4
Temperature for
Hardware
0~50℃, relative humidity 20-90% RH
(non-condensing)
Storage Temperature of
Hardware
-20~60℃
Vibration
0.5mm displacement, 10-55Hz, X, Y, Z three
directions and two hours for each direction
Impact
10G, 11ms, from X, Y, Z three directions and three
times for each direction
Radiated Emission CISPR22, Class A
Electrostatic Discharge
Immunity
EN61000-4-2/1995
Radiated Immunity EN61000-4-3/1995
Electrical Fast
Transient
EN61000-4-4/1995
Weight / Dimension
0.24kg / 147×97×35.5mm
(Weight(W)×Height(H)×Deep(D))
Cooling Method Natural air-cooling
The Function of Program Copy Card
Function of program copy card TP04G provides to copy user program, system
function and passwords is different from the regular copy program. It is used to
copy the whole HMI environment settings and application programs to another
HMI rapidly. It saves time and manpower. The operation is as follows.
Definition: program copy card PCC, TP Series TP.
Step Copy HMI program to PCC
(TPPCC)
Copy program in PCC to HMI
(PCCTP)
1
Turn the switch on the PCC to
TPPCC
Turn the switch on the PCC to
PCCTP
2
Insert the PCC into the extension
slot of TP
Insert the PCC into the extension
slot of TP
3 Input the power to TP Input the power to TP
4
It will display “remove PCC” on the
screen and power on again
It will display “remove PCC” on the
screen and power on again
HMI Display Message
Copy HMI program to PCC (TPPCC)
Copy PCC program to HMI
(PCCTP)
If the model type of TP does not
correspond with the model type of program
of PCC, TP will display “TP series and
PCC is different Press Enter to Confirm
TP seriesPCC Press Esc to Exit”.
If there is no program in PCC, TP
will display “The PCC is Empty
PCCTP series is illegal”.
TP will display “TP PCC series Please
wait !” during transmission.
TP will display “PCCTP series
Please wait !” during transmission.
TP will display “Please Remove the PCC
and Reboot” when completing transmitting.
TP will display “Please Remove
the PCC and Reboot” when
completing transmitting.
Hardware Operation
The steps to Startup the TP04G:
1. Connect power line,
2. Apply 24V DC power,
3. Enter into the startup display,
4. Enter the user-designed program
5. Press ESC key and hold on for 5 seconds to return to system menu.
There are five selections in the system menu and are described below.
Download
Program
Use the connection cable (DVPACAB530) to connect the serial
communication port RS-232 of TP04 to a PC. Then use the
TPEdit software to download an application program to the TP04.
Upload
Program
Use the connection cable (DVPACAB530) to connect the serial
communication port RS-232 of TP04 to a PC. Then use the
TPEdit software to upload an application program from the TP04.
Copy
Program
Transfer a program between two TP04 units.
1: transmit programs
2: receive programs
When transmitting programs and data between two TP04 units.
Set one TP04 to “Receive Program” mode and the other TP04 to
“Transmit Program” mode. Please use twisted pair wires to
connect the two units via the RS-485 ports.
TP04
Settings
There are 8 items that used to modify TP04 system settings:
1. Communication protocol: Setting the address of TP04, the
control port, and the communication string for either RS-232 or
RS-485.
2. Contrast: Adjust the contrast of LCM display screen.
3. Back-light: adjust the automatic turn off time of LCM.
Factory setting is 01, setting range is 00~99 seconds. If set to
00, the LCM Back-light will not turn off.
4. Date and Time: It is used to set the TP04 built-in RTC including
year, month, day, hour, minute, second and week. Also the
internal battery capacity display is shown here.
5. Buzzer: Used to set the buzzer sound, normal mode or quiet
mode.
6. Language Setting: Used to set the displayed language.
English, Traditional Chinese, simplified Chinese or user
defined language.
7. Password setting: Used to set, enable, and disable the
password function. If the password function is enabled, user
then needs to input a password before the system menu may
be accessed. The factory password is 1234.
8. Startup display: Used to select the TP04 startup display.
Execution
Execute the internal program. When entering execution
program, you can return to system menu by pressing Escape/Exit
(Esc) key for 5 seconds.
PLC
Connection
There are two methods to connect to PLC:
1. Use the connection cable (DVPACAB215 or DVPACAB230)
to connect program communication I/O RS-232C of PLC to
serial communication port (COM1) RS-232 of TP04.
2. Use twisted cable to connect RS-485 of PLC to extension
communication port (COM2) RS-485.
Password Functions
1. If user forgot the password, password then can be cleared via using the
following code: 8888. This universal code will clear the password and all
TP04 internal programs. The TP04 will be reset to the factory settings.
2. Users may use 0~9 and A~Z as characters for the password. Users
must use the function keys F0~F4 to input the password characters.
F0: scrolls in a loop as follows 0 5 A B C D E F 0
F1: scrolls in a loop as follows 1 6 G H I J K 1
F2: scrolls in a loop as follows 2 7 L M N O P 2
F3: scrolls in a loop as follows 3 8 Q R S T U V 3
F4: scrolls in a loop as follows 4 9 W X Y Z 4
Functional Specification
TP04G-AS1
Screen STN-LCD
Color Monochromatic
Back-light
The back-light automatic turn off time is 1~99 minutes
(0 = do not to turn off)
(back-light life is about 50 thousand hours at 25℃)
Resolution 128X64 dots
Display Range 67 mm (W) X 32 mm (H), 3” diagonal preferred
Contrast
Adjustment
10-step contrast adjustment
Language Font
ASCII: characters (including European Fonts)
Taiwan: (BIG 5 code) traditional Chinese character font
China: (GB2324-80 code) simplified Chinese character
font
Font Size(ASCII) 5 X 8, 8 X 8, 8 X 12, 8 X 16
5 X 8: 25 words X 8 rows
8 X 8: 16 words X 8 rows
8 X 12: 16 words X 5 rows
Maximum words
x rows, for each
font size
8 X 16: 16 words X 4 rows
ALARM
Indication LED
1. Power on indication (Flash three times)
2. Flash for communication error or other alarm
3. Special Indication by user programming
RS-232 Indication
LED (Yellow)
It will be flashing when transmitting program and
communicating by using RS-232.
Display Screen
RS-485 Indication
LED (Green)
It will be flashing when communicating by using RS-485.
Program Memory 256KB flash memory
Serial
Communication
(COM1)
Unsynchronized transmission method: RS-232
Data length: 7 or 8 bits
Stop bits: 1or 2 bits
Parity: None/Odd/Even
Transmission speed: 9600bps~115200bps
Extension
Communication
port
(COM2)
Unsynchronized transmission method: RS-485
Data length: 7 or 8 bits
Stop bits: 1 or 2 bits
Parity: None/Odd/Even
Transmission speed: 9600bps~115200bps
Extension Slot 1. Update program version 2.The slot for program copy
card
Battery Cover DC 3V battery for HMI
External Interface
5-pin terminal There are DC 24V input and RS-485 input
Communication Connection
TP04G may connect to a PC by using connection cable
DVPACAB530
1
5
6
9
9 PIN D-SUB
PC TP04G
ON PC (RS-232)
ON TP04G
5
1
9
6
9 PIN D-SUB
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
RX
TX
RX
TX
GND
TP04G may connect to the DVP-PLC by using cable DVPACAB215
(1.5 m) or DVPACAB230 (3.0 m without 25 pin D-SUB).
PC or TP04G
PLC(DVPACAB215)
11
1313
1414
1
5
6
9
25 PIN D-SUB
9 PIN D-SUB
9 PIN D-SUB
PC or TP04G end
6
8
20
4
5
7
2
3
1
2
3
4
5
6
7
8
9
GND
TX
RX
Pin 2:TX
Pin 3:RX
Pin 7:GND
Pin 2:RX
Pin 3:TX
Pin 5:GND
Socket
8 PIN MINI DIN
ON PLC
ON PLC
8 PIN MINI DIN
1
2
3
4
5
6
7
8
Pin 1,2:5V
Pin 3,6,8:GND
Pin 4:RX
Pin 5:TX
Pin 7:+24V
25 PIN D-SUB