DELTA DOC CENTER 9 Fig 2-1.2 Front Panel for 2KVA or 3KVA 2-5 OPERATION PANEL Fig 2-2 Operation Panel OPERATION PANEL A. Button: 1. 1/TEST: The but
DELTA DOC CENTER 10 2. Line: The LED indicates the condition of UPS input line. If the input voltage is too low, too high or out of frequency this LED
DELTA DOC CENTER 11 2.6 REAR PANEL The rear panel is explained as follows: (Please refer to fig 2-3, 2-4) Fig 2-3 700VA, 1KVA Fig 2-4 2KVA, 3KVA 1.
DELTA DOC CENTER 12 2. I/P BREAKER: This is used to prevent high input current from the UPS. 3. INPUT SOCKET or TERMINAL: AC input utility power sup
DELTA DOC CENTER 13 3. INSTALLATION 3-1 Unpacking zPlease read this user manual before installing the UPS. zThis UPS contains batteries which are
DELTA DOC CENTER 14 (2) Plug the other end of the power cord into a two-pole, three-wire, grounding receptacle only. Avoid using extension cords and
DELTA DOC CENTER 15 3. Charging the battery { The battery charger of the UPS automatically charges the battery whenever the power cord of UPS is co
DELTA DOC CENTER 16 { Turn on the equipment connected to the UPS. { Caution: Do not connect a laser printer to the UPS. { Caution: Do not conne
DELTA DOC CENTER 17 Fig 3-4.2 UPS Connection for 2KVA or 3KVA: (1) RS-232/Dry contact cable. (2) Provides power to PC. (3) Connected to utility power
DELTA DOC CENTER 18 4. OPERATION 4-1 Cold start when utility is not present Even when there is no utility power, you can still turn on the UPS. Just
DELTA DOC CENTER 1 1. IMPORTANT SAFETY INSTRUCTIONS 1-1 UL safety instructions SAVE THESE INSTRUCTIONS - This manual contains important instructions
DELTA DOC CENTER 19 4-4 UPS self-test If press the 1/TEST button when the UPS is in “ON-LINE mode”, it will make the UPS shift to “ON-BATTERY mode” a
DELTA DOC CENTER 20 { BATTERY REPLACE: This LED function is to alert user that the batteries should be replaced. When the microprocessor in the UPS
DELTA DOC CENTER 21 4-7 UPS internal fault If the following conditions occur, the UPS fails. At this time the UPS will transfer to “BYPASS mode”. The
DELTA DOC CENTER 22 5. MAINTENANCE zNormally, the life of battery is 3 years. But extreme operating condition and environment may shorten its life-
DELTA DOC CENTER 23 6. PLACEMENT To stably install the UPS, the 2,3KVA must add stands to support themselves. The installation method is as shown be
DELTA DOC CENTER 24 7. TROUBLESHOOTING Problem Possible Cause Solution ON/TEST button is not pushed. Press the 1/TEST button to turn on the UPS. (
DELTA DOC CENTER 25 The exhaust fans and ventilation grills may be obstructed. Choose a well-ventilated area to position your UPS to allow adequate d
DELTA DOC CENTER 26 8. COMMUNICATION INTERFACE The UPS provides RS-232 and Dry contact protocols in one D-sub 9 connector. Using proper UPS managemen
DELTA DOC CENTER 27 The RS-232 communication port provides the following functions: 1) Monitoring charger status 2) Monitoring battery status and con
DELTA DOC CENTER 28 Its major functions normally some or all of following: To broadcast a warning when power fails. To close the files before
DELTA DOC CENTER 2 Other safety notes: - Examine the packing container for damage. Notify the carrier immediately if damage is present. - Do not disa
DELTA DOC CENTER 29 Technical specifications Model GES701N GES102N GES202N GES302N Capacity 700VA/560W 1KVA/800W 2KVA/1600W 3KVA/2400W Rated Vo
SHEET 31 TO END
DELTA DOC CENTER 3 1-2 TUV safety instructions Please observe the following precautions to ensure personnel safety and reliable equipment operation:
DELTA DOC CENTER 4 - A battery can present a risk of electric shock and high short circuit current. The following precaution should be observed when
DELTA DOC CENTER 5 2 INTRODUCTION 2-1 Theory of operation The main topology of the UPS consists of bypass path, AC-DC converter, DC-AC inverter, bat
DELTA DOC CENTER 6 In case the utility power fail, the AC-DC converter and charger will be off duty. The DC-DC converter works and converts the batter
DELTA DOC CENTER 7 Intelligent design Integrated with a microprocessor, the UPS is able to perform intelligent functions. The UPS triggers over-volta
DELTA DOC CENTER 8 2-3 Annotation and symbol The two signs shown on the manual indicating important instruction need to be followed. Read before O