Delta Electronics DTB4896 Spezifikationen Seite 4

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 8
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 3
Input Sensor Type Register Value Display Range
Thermocouple R type 5
0 ~ 1,700°C
Thermocouple N type 4
-200 ~ 1,300°C
Thermocouple E type 3
0 ~ 600°C
Thermocouple T type 2
-200 ~ 400°C
Thermocouple J type 1
-100 ~ 1,200°C
Thermocouple K type 0
-200 ~ 1,300°C
Note 1: The current input is built-in with a 249 precision resistor. See “How to Set up Current Input” section.
Note 2: The default setting is Pt100 input.
Note 3: To display the decimal point, you have to set up the parameter
(in the operation mode). The decimal point display is available for all modes
except for thermocouple B, R, and S type.
Note 4: The range for analog input is -999 ~ 9,999. Take 0 ~ 20mA for example, -999 refers to 0mA input and 9,999 refers to 20mA input. If we change the
range into 0 ~ 2,000, 0 will thus refer to 0mA input and 2,000 refers to 20mA input (1 display scale = 0.01mA).
Alarm Output
DTV offers 2 groups of alarm outputs and 17 modes for each group under the initial setting mode. When the PV exceeds or falls below SV, the alarm output
will be enabled. See the table below for the 17 alarm output modes.
Mode Alarm Type Alarm Output Operation
0
No alarm
Off
1
Alarm output is enabled when the temperature reaches upper and lower limits.
Alarm will be enabled when the PV exceeds SV + AL-H or falls below SV - AL-L.
ON
OFF
AL-L SV AL-H
2
Alarm output will be enabled when the temperature reaches the upper limit.
Alarm will be enabled when the PV exceeds SV + AL-H.
ON
OFF
SV
AL-H
3
Alarm output is enabled when the temperature reaches the lower limit.
Alarm will be enabled when the PV falls below SV – AL-L.
ON
OFF
AL-L
SV
4 Alarm output will be enabled when the PV is between SV + AL-H and SV – AL-L.
ON
OFF
AL-L SV
AL-H
5
Alarm output is enabled when the temperature reaches the absolute value of the upper and lower limits.
Alarm will be enabled when the PV exceeds AL-H or falls below AL-L.
ON
OFF
AL-L
AL-H
6
Alarm output is enabled when the temperature reaches the absolute value of the upper limit.
Alarm will be enabled when the PV exceeds AL-H.
ON
OFF
AL-H
7
Alarm output is enabled when the temperature reaches the absolute value of the lower limit.
Alarm will be enabled when the PV falls below AL-L.
ON
OFF
AL-
L
8
Standby upper/lower limit alarm: Alarm will be enabled when the PV reaches SV and exceeds SV + AL-H or
falls below SV – AL-L.
ON
OFF
AL-L
AL-H
SV
9 Upper limit standby alarm: Alarm will be enabled when the PV reaches SV and exceeds SV + AL-H.
ON
OFF
SV AL-H
10 Lower limit standby alarm: Alarm will be enabled when the PV reaches SV and falls below SVAL-L.
ON
OFF
AL-L SV
11
Upper limit hysteresis alarm: Alarm will be enabled when the PV exceeds SV + AL-H. Alarm will be disabled
when the PV falls below SV + AL-L.
ON
OFF
AL-L
AL-H
12
Lower limit hysteresis alarm: Alarm will be enabled when the PV falls below SV – AL-H. Alarm will be
disabled when the PV exceeds SV – AL-L.
ON
OFF
AL-L
AL-H
14 Programmable STOP: Alarm will be enabled when the program is in STOP status.
15 Programmable RAMP UP: Alarm will be enabled when the program is in RAMP UP status.
16 Programmable RAMP DOWN: Alarm will be enabled when the program is in RAMP DOWN status.
17 Programmable SOAK: Alarm will be enabled when the program is in SOAK status.
18 Programmable RUN: Alarm will be enabled when the program is in RUN status.
Note: AL-H and AL-L include AL1H, AL2H and AL1L, AL2L. There is no mode 13 (reserved for CT function).
PID Programmable Control
Functions and Parameter Setting:
The PID programmable control includes 8 patterns (Pattern 0 ~ 7). Each pattern contains 8 steps (Step 0 ~ 7) and parameters: link pattern, cycle and the
number of steps.
Start Pattern
: This parameter can be set in the operation mode. The user can set up which pattern is the start pattern for the programmable control.
This function is only available when the program is in STOP status.
Step: Includes the settings of the two parameters, set point X and execution time T, indicating that the set point (SV) has to rise to temperature X after the
period of execution time T. If the result of the set point X is the same as that of the previous setting, the process is called Soak; otherwise, it is called Ramp.
Therefore, the programmable control is also known as Ramp/Soak control.
The default setting of the first step program is Soak control. The temperature will first rise to the set point X and remain at X. The total execution time is T.
Link Pattern: For example, if the parameter
is set as 2, it refers to the execution of pattern 2 will follow the execution of pattern 0. If the link pattern
is set as
, it refers to the program will end after the execution of the pattern is completed and the temperature will remain at the SV for the last step.
Cycle: The additional number of cycles for a pattern. For example, if the parameter
is set as 2, it refers to pattern 4 has to execute twice
additionally, totaling the executions to 3 times including the original one.
4
Seitenansicht 3
1 2 3 4 5 6 7 8

Kommentare zu diesen Handbüchern

Keine Kommentare