Delta Electronics AC Motor Drive VFD-VE Series Spezifikationen Seite 41

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 182
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 40
5
VFD-V Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-13
5.2 Group 1: Basic Parameter
01-00 Maximum Output Frequency Factory setting 60.00/50.00
Settings 50.0~400.00Hz
This parameter determines the drive’s maximum output frequency.
01-01 Maximum Voltage Frequency (Base Frequency) Factory setting 60.00/50.00
Settings 0.00~400.00 Hz
This parameter must be set to the motors nameplate frequency rating.
01-02 Maximum Output Voltage
Settings 230V: 0.0~255.0V Factory setting 220.0
460V: 0.0~510.0V
Factory setting
440.0
This parameter must be set to the motors nameplate voltage rating.
01-03 Upper Midpoint Output Frequency Factory setting 0.50
Settings 0.00~400.00Hz
01-04 Upper Midpoint Output Voltage
Settings 230V: 0.0~255.0V
a
Factory setting 5.0
460V: 0.0~510.0V
a
Factory setting 10.0
01-05 Lower Midpoint Output Frequency Factory setting 0.50
Settings 0.00~400.00Hz
01-06 Lower Midpoint Output Voltage
Settings 230V: 0.0~255.0V
a
Factory setting 5.0
460V: 0.0~510.0V
a
Factory setting 10.0
01-07 Minimum Output Frequency Factory setting 0.00
Settings 0.00~400.00Hz
01-08 Minimum Output Voltage
Settings 230V: 0.0~255.0V
a
Factory setting 0.0
460V: 0.0~510.0V
a
Factory setting 0.0
Setting of the V/F curve figure is usually based upon the motor’s allowable loading
characteristics. Pay special attention to the motors heat dissipation, dynamic balance,
and bearing lubricity, if the loading characteristics exceed the loading limit of the motor.
CALL NOW 800-985-6929
http://www.automatedpt.com
CALL NOW 800-985-6929
http://www.automatedpt.com
Seitenansicht 40
1 2 ... 36 37 38 39 40 41 42 43 44 45 46 ... 181 182

Kommentare zu diesen Handbüchern

Keine Kommentare