VFD-L Series User Manual 115V 200W-400W 230V 200W-2HP Simple General Purpose AC Drive ASIA DELTA ELECTRONICS, INC. TAOYUAN
9Group 3: Output Function Parameters Parameters Functions Settings Factory Setting 3-00 Desired freq. attained 1.0 ~ 400 Hz 1.0 3-01 Termin
10 Parameters Functions Settings Factory setting 4-06 Multi-function input 7 terminal 3(M3) (d 0, d 4〜d 20) 14: increase m
11 Parameters Functions Settings Factory Setting 6-04 Over-torque detection time 0.1 ~ 10.0 Sec 0.1 6-05 Electronic thermal overload relay 0: Not
12 Parameters Functions Settings Factory Setting 8-05 Max. allowable power loss time 0.3 ~ 5.0 Sec 2.0 8-06 B.B. time for speed search 0.3~5.0
13CHAPTER 4 Troubleshooting and Fault Information The VFD-L AC drive has a comprehensive fault diagnostic system that includes several different ala
14Fault Name Fault Descriptions Corrective Actions Over-current during acceleration: 1. Short-circuit at motor output. 2. Torque boost too high.
15Standard Specifications Voltage Class 115V 230V Model Number VFD-LA/B 002 004 002 004 007 015 Applicable Motor Output (kW) 0.2 0.4 0.2
1Preface Thank you for choosing DELTA’s VFD-L series AC Drive. The VFD-L series is manufactured using high-quality components, material and incorpo
2Chapter 1 Receiving and Inspection This VFD-L AC drive has gone through rigorous quality control tests at the factory before shipment. Since many t
3Dimension RARC + 10VAVIM0M1M2M3GNDSTOPRUNFWDREVRUNSTOPPROGDATAMODERESETDo not connect AC power to outputWARNINGRead the user manual before operation
4Chapter 2 Wiring Basic Wiring Diagram Users must connect wiring according to the circuit diagram shown below. Please follow all National and State
5Main circuit wiring Single phase models input from R/L1, S/L2AC line input terminalsgroundingUP/DOWNFunction Display keyData Confirmation keyRU
6Wiring Notes: PLEASE READ PRIOR TO INSTALLATION. 1. ! CAUTION: Do not connect the AC input to any of the U/T1, V/T2, W/T3 terminals, as it will dama
7Chapter 3 Summary of Parameters Group 0: User Parameters aThe parameter may be set during operation. Parameters Functions Settings Factory Sett
8 Parameters Functions Settings Factory Settinga 1-12 Decel time 2 0.1 ~ 600 Sec 10.0 a 1-13 JOG Accel time 0.1 ~ 600 Sec 10.0 a 1-14 JOG De