2 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 2-1CHAPTER 2 STORAGE AND INSTALLATION 2.1 Storage The AC drive should be kept in the s
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-67Content Address Function 2104H Output current (AXXX.X) 2105H DC-BUS Voltage (UXXX
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-68The explanation of exception codes: Exception code Explanation 01 Illegal function code:
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-695.11 Group 10: PID Control Parameters 10 - 00 Input Terminal for PID Feedback Factory
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-70 When this parameter is set to 01: when positive control, the deviation equation is dev
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-71 Settings 0.0~2.5 Sec Unit: 0.1 This parameter determines primary Low Pass filter t
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-72 10-12 PID Mode Selection Factory setting 00 Setting Range 00 Manual gain control mod
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-735.12 Group 11: Fan and Pump Control Parameters 11 - 00 V/f Curve Selection Factory Set
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-74 11 - 01 Circulative Control Factory Setting: 00 Settings 00: No function 01: Time circul
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-75 ContactorM1U V W ContactorM2 ContactorM3 ContactorM4 RA2 RB2 RC2 RA1 RB1 RC1 RA5 RC5
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-76 ContactorContactor M1 R S TU V W ContactorContactor M2 ContactorContactor M3 ContactorCo
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 2-22.2 Installation CAUTION The control, power supply and motor leads must be laid separatel
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-77When 1st and 2nd motors are running, if VFD-F output frequency continually surpasses 1
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-78 When the setting is <<03 Fixed amount control (one AC drive runs with 8 motors)
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-7903-03 N/A N/A N/A 04 Motor 4 runs by AC drive.N/A 04 Motor 2 runs by commercial power.
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-80 11 - 04 Motor Switch Delay Time Factory Setting: 1.0 Settings 0.0~3600.0 sec Unit: 0
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-81 11 - 06 Motor Switch Frequency during Fixed Amount CirculationFactory Setting: 60.00
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-82NOYESNOYEST3=T3+1T3=(11-04)PIDcalculates FN+1 ONT3 0T3=T3+1T3=(11-04)N+2 ONT3 0Fixed am
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-8311 - 09 Wake Up Frequency of Sleep Process Factory Setting: 0.00 Settings 0.00 to 1
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-84 11 - 10 Treatment of Fixed Amount Circulation Malfunction Factory Setting: 00 Settings
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-85 11 - 11 Stop Frequency of Auxiliary Motor Factory Setting: 0.00 Settings 0.00~120.00
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-86Fire Mode: The error code of AC drive under normal usage and fire mode Code
3 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-1CHAPTER 3 WIRING DANGER Hazardous Voltage Before accessing the AC drive: Disconn
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-8722 PHL X 23 Lc X 24 FbL X 26 FANP X 27 Fan1 Abnormal X 28 Fan2 Abnormal
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-88 11-18 Bypass Function Factory Setting 00 Setting Range 00 Turn Off 01 Turn
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-89speedErrors occurredP 11 17 Number of Times of Reactivationcaused by unusual Fire Mode
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-90 coast to stopMotor 1 Motor 2 Motor 3 Motor 4 VFD-F operation time freq by VFD-F by VFD-F
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-91 Example of Fixed Time Circulation: Connecting 4 Motors Contactor M1 U V W Contac
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-92Pr11-01=02 Fixed Amount Circulation When Motor#1 of the inverter accelerate from 0Hz to
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-93 Motor 1 Motor 2 Motor 3 Motor 4 VFD-F operation
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-94 Motor 3 Motor 2 Motor 1 Motor 4 VFD-F operation dem and freq dem and output (flow
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-95 Example of Fixed Amount Circulation: Connecting to 4 motors ContactorContactor M1
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-96Pr11-01=03 Fixed Amount Control The motor powered by the inverter accelerates from 0Hz t
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-23.1 Basic Wiring Diagram Users must connect wires according to the following circuit diagr
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-97 Pump 0Pump 1Pump 2Pump 3VFD-F operation of first
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-98 Pump 0Pump 1Pump 2Pump 3VFD-F operation of first pu
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-99 Example of Fixed Amount Control: Connecting to 4 motors R S TU V W Contactor M1 R
6 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 6-1CHAPTER 6 MAINTENANCE AND INSPECTIONS Modern AC drives are based on solid state ele
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED This page intentionally left blank.
7 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 7-1CHAPTER 7 Troubleshooting and Fault Information The AC drive has a comprehensive faul
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 7-2Fault Name Fault Descriptions Corrective Actions The AC drive temperature sensor detects
7 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 7-3Fault Name Fault Descriptions Corrective Actions OC hardware error Return to the fact
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 7-4Fault Name Fault Descriptions Corrective Actions Analog Signal Error 1. Check ACI wiring
7 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 7-5Fault Name Fault Descriptions Corrective Actions Ground fault: The AC drive output is
3 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-3*RS-485R(L1)S(L2)T(L3)NFBRSTRBRC+1 +2SAOFFONMCMCE1:+EV2:GND3:SG-4:SG+5:NC6:NCMI1MI2MI3M
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 7-6Fault Name Fault Descriptions Corrective Actions Fan 1, 2, 3 fault (150~300HP) Remove any
8 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-1CHAPTER 8 PARAMETER SUMMARY Group 0 AC Drive Status Parameter Parameters Functions Se
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-2 Parameters Functions Settings Factory Setting Customer 00-02 AC Drive Status Indicatio
8 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-3Group 1 Basic Parameter (Twice the value for 460V class) Parameters Functions Setting
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-4Group 2 Digital Output/Input Parameter Parameters Functions Settings Factory Setting Cus
8 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-5 Parameters Functions Settings Factory Setting Customer 02-07 Loss of ACI Signal 0
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-6 Parameters Functions Settings Factory Setting Customer 02-13 Master Frequency Memory Se
8 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-7Group 3 Output Function Parameters Parameters Functions Settings Factory Setting Cust
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-8 Parameters Functions Settings Factory Setting Customer 37: PLC program operation Pa
8 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-9Group 4 Input Function Parameters Parameters Functions Settings Factory Setting Custo
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-4Wiring for SINK mode and SOURCE mode JOG1/2 Accel/Decel switchMI7MI8 Sw1SinkSourceJO
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-10 Parameters Functions Settings Factory Setting Customer 04-07 Multi-function Input ter
8 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-11 Parameters Functions Settings Factory Setting Customer 04-12 AVI Maximum frequency
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-12Group 5 Multi-step Speed Frequency Parameters Parameters Functions Settings Factory Set
8 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-13 Parameters Functions Settings Factory Setting Customer 05-30 Time Duration Step 14
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-14Group 6 Protection Function Parameters (Twice the value for 460V class) Parameters Funct
8 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-15 Parameters Functions Settings Factory Setting Customer 05: oL1 (over load 1) 06: EF
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-16 Parameters Functions Settings Factory Setting Customer 06-18 Recording Mid/Low Voltage
8 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-17Group 8 Special Parameters (Twice the value for 460V class) Parameters Functions Set
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-18Group 9 Communication Parameters Parameters Functions Settings Factory Setting Customer
8 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-19 Parameters Functions Settings Factory Setting Customer09-06 Communication Operation
3 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-53.2 External Wiring R/L1S/L2T/L3U/T1V/T2W/T3B2-+/B1EEBRVFDBBREMI FilterPower SupplyFUSE
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-20Group 10 PID Controls Parameters Functions Settings Factory Setting Customer 10-00 In
8 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-21Group 11 Fan and Pump Control Parameters Parameters Functions Settings Factory Setti
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED This page intentionally left blank.
A VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED A-1Specifications Voltage Class 230V Class Model Number VFD-_ _ _F23_ 007 015 022 037 055
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED A-2Other Functions AVR, 2 kinds of S-Curve, Over-Voltage, Over-Current Stall Prevention, Faul
B VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-1 ACCESSORIES B.1 All Brake Resistors & Brake Units Used in AC Motor Drives Note: Pl
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-2NOTE 1. Please select the brake unit and/or brake resistor according to the table. “-“ me
B VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-3 B.1.1 Dimensions and Weights for Brake Resistors (Dimensions are in millimeter) Order
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-4Order P/N: BR500W030, BR500W100, BR1K0W020, BR1K0W075 TYPE L1 L2 H D W MAX. WEIGHT(g)BR50
B VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-5 B.1.2 Specifications for Brake Unit Voltage Class 230V Series 460V Series Model Numb
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-63.3 Main Circuit Connection Figure 1 for the main circuit terminals R(L1)S(L2)T(L3)RSTU(T1
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-6B.1.3 Dimensions for Brake Unit (Dimensions are in millimeter[inch]) Figure 1: VFDB2015, V
B VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-7 Figure 2: VFDB4132 VFDB4132CHARGE ACT OC OH
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-8B.2 AMD-EMI Filter Cross Reference AC Drives EMI Model NumberVFD007F23A/H, VFD015F23A/H,
B VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-9 Remove any paint on metal saddle for good ground contact with the plate and shielding
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-10B.3 AC Reactor AC Input Reactor Recommended Value 460V, 50/60Hz, 3-Phase Inductance (mh
B VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-11 AC Output Reactor Recommended Value 230V, 50/60Hz, 3-Phase Inductance (mH) kW HP Fund
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-12B.4 Non-fuse Circuit Breaker Chart The fuse should comply with UL248 and the breaker shou
B VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-13B.5 Fuse Specification Chart Smaller fuses than those shown in the table are permitted
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-14B.6 PU06 B.6.1 Description of the Digital Keypad VFD-PU06 UFHVFD-PU06JOGRUNRESETSTOPLED
B VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-15Display Message Descriptions The specified parameter setting. The actual value store
3 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-7Mains power terminals (R/L1, S/L2, T/L3) Connect these terminals (R/L1, S/L2, T/L3)
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-16B.7 Relay Card Specifications: 1. Screw Length (between RELAY CARD and Control Board): 8
B VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-17PCB-SUPPORTPCB-SUPPORT CONTROL-BOARDPCB-SUPPORTINSULATORRELAY-CARDSCREW M3*P0.5TORQUE=
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-18B.8 Zero Phase Reactor (RF220X00A) Dimensions are in millimeter and (inch) Reco
C VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-1 DIMENSIONS Frame B HW1DH1WD1S2S1 UNIT: mm [inch] Frame W W1 H H1 D D1 S1 S2 B1
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-2Frame C W1WH1HS2DD2D1S1 UNIT: mm [inch] Frame W W1 H H1 D D1 D2 S1 S2 C1 200.0 [7.88] 185.
C VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-3 Frame D WW1HH1DS1D2D1 UNIT: mm [inch] Frame W W1 H H1 D D1 D2 S1 D1 250.0 [9.84
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-4Frame E W1WH1H2HDS2D1S1D2S3 UNIT: mm [inch] Frame W W1 H H1 H2 D D1 D2 S1 S2 S3 E1 370.0 [
C VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-5 Frame G W1WH1HD1H2D2S2HJOGURUNMODEPROGRESETSTOPDATAJOGRUN STO P REVVFD-PU01FWDFS1DS3S4
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-6Frame H W1WH1HD1H2D2S2HJOGURUNMODEPROGRESETSTOPDATAJOGRUN STO P REVVFD-PU01FWDFS1DS3S4 UNI
C VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-7 VFD-PU01 Unit: mm (inches) 6.5 [0.26]19.0 [0.75]110.0 [4.33]73.0 [2.87]97.0 [3.82]44.0
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-8Terminals [+2/B1, B2] for connecting brake resistor and terminals [+2/B1, -] for connectin
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-8KPF-CC01 Unit: mm (inches)
FE0 950 116 1300 920 11 - 04- 18
3 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-93.4 Control Terminals +24VDCMSINK/NPN ModeMulti-functionInput TerminalInternal Circuit
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-10Terminal Symbols Terminal Functions Factory Settings +10V Potentiometer power source +10
3 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-113.5 Specifications for Power Terminals and Control Terminals Frame B +1+2B1-B2R/L1 S/L
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-12Frame D 3IMPOWER - ( ) ( ) + DC DC MOTORPower Terminals: R/L1, S/L2, T/L3, U/T1, V/T2,
3 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-13Frame G POWER DC(+)IMMOTORDC(-)3V/T2S/L2R/L1 +2T/L3 +1 U/T1 W/T3 Power Terminals: R/L1
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-143.6 Wiring Notes: PLEASE READ PRIOR TO INSTALLATION. 1. ! CAUTION: Do not connect the AC
3 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-1513. For the single-phase rated AC drives, the AC power can be connected to any two of
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-163.7 Motor Operation Precautions 1. When using the AC drive to operate a standard 3-phase
4 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4-1CHAPTER 4 DIGITAL KEYPAD OPERATION This chapter describes the various controls and i
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4-24.1 VFD-PU01 4.1.1 Description of the Digital Keypad VFD-PU01 UFHVFD-PU01JOGLED DisplayDi
4 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4-3Display Message Descriptions Display the AC drive forward run status. The AC drive r
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4-44.1.3 Operation steps of the Digital Keypad VFD-PU01 MODEMODEMODEMODEMODEMODE STARTUFHSele
4 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4-54.2 KPF-CC01 For models of VFD-F (HVAC) series VFD007F43H; VFD015F43H; VFD022F43H; VFD0
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4-6Display Message Description The output current present at terminals U, V, W. The specif
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-1CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS : This parameter can be set during operati
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-2Code AC Drive Status Explanation 26 FAnP Fan Power Fault 27 FF1 Fan 1 Fault 28 FF2 Fa
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-3 00 - 08 Output Power Factor Factory setting: Read Only This parameter displays
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-45.2 Group 1: Basic Parameters 01 - 00 Maximum Output Frequency Factory Setting: 60.0
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-501 - 04 Mid-point Voltage Factory Setting: 5.5/11.0 Settings 230V series: 0.1 ~
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-6Output voltageOutput Frequency01-0201-0401-0601-0001-0701-0801-0101-05 01-03 01 - 09 Acce
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED Preface Thank you for choosing DELTA’s high-performance VFD-F Series. VFD-F Series are manu
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-701 - 19 JOG Frequency Factory Setting: 6.00 Settings 0.0 Hz~120.00 Hz Unit: 0.
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-801 - 23 Accel/Decel Time Unit Factory Setting: 01 Settings 00: Unit is 1 Sec 01: Unit is
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-95.3 Group 2: Operation Method Parameters 02 - 00 Source of Frequency Command Factory S
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-1002 - 02 Stop Method Factory Setting: 00 Settings 00:Stop = ramp to stop, E.F. (Externa
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-11 The Carrier frequency of the PWM output has a signification influence on the electr
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-1202 - 06 Line Start Lockout Factory Setting: 01 Settings 00: Enabled 01: Disabled 02:
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-13 To program this parameter the user must first generate a Hex value with the informa
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-14 02 - 10 User Defined Coefficient Factory Setting: 1.00 Settings 0.01~160.00 Uni
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-15 02-14 Source of Second Frequency Command Factory Setting 00 Setting Range 00Maste
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-165.4 Group 3: Output Function Parameters 03 - 00 Multi-function Output terminal 1 (Relay 1
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED TABLE OF CONTENTS CHAPTER 1 RECEIVING AND INSPECTIONS 1.1 Nameplate Information ...
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-17Setting Functions Descriptions 21 Low voltage detection The corresponding output w
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-18Setting Functions Descriptions 40 HOA-Off mode indication Under the Off mode indication
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-19 03 - 10 Analog Output 1, (AFM1) 0~10Vdc Factory Setting: 00 03 - 11 Analog Output 2,
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-20 03 - 15 DC Fan Control Factory Setting: 00 Settings 00: Fan runs on power up. 01: Fan be
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-215.5 Group 4: Input Function Parameters 04 - 00 Multi-function Input terminal 1 Factory
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-22Setting Functions Descriptions 14 Decrease Frequency frequency command. This terminal
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-23Setting Functions Descriptions 32 Run PLC Program 33 Pause PLC Program Parameter valu
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-24 04 - 08 Digital Input Terminal Response Time Factory Setting: 01 Settings 01~20 This
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-2504 - 19 ACI2 Minimum frequency (percentage of Pr.1-00) Factory Setting: 0.0004 - 20
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-26Pressure PaAnaloginput10-10=10.0 Pa04-12=70AVIACI2ACI104-16=5004-20=4004-11=3004-15=004-1
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4.2 KPF-CC01 ...
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-27 04 - 24 Summation of External Frequency Sources Factory Setting: 00 Settings 00: No f
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-28 5.6 Group 5: Multi-step Speed Frequency Parameters 05 - 00 1st Step Speed Frequency Fac
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-29Example 1 (Pr.05-15 = 1): Execute one cycle of the PLC program. Its relative parameter
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-30The example below shows how the PLC can perform one cycle at a time, within in a complete
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-31123456789101112131415 0WeightsBit0=Forward1=ReverseDirection of Pr.05-001st speed for
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-3205 - 17 Time Duration of 1st Step Speed Factory Setting: 0.005 - 18 Time Duration of 2n
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-3305-05FrequencyMaster Speed05-0005-0105-0205-0305-0405-0605-0705-0805-0905-1005-1105-12
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-345.7 Group 6: Protection Function Parameters 06 - 00 Over-voltage Stall Prevention Factor
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-35Over-current StallPrevention during acceleration06-01CurrentOutput frequencyOver-curre
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-3606 - 03 Over-torque Detection Selection Factory Setting: 00 Settings 00: Over-torque dete
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED CHAPTER 8 SUMMARY OF PARAMETER SETTINGS ... 8 - 1 APPENDIX A S
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-37chart below. The actual reaction time will vary depending on output current. 1234560H
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-38 08 CPU failure (cF3) 09 Hardware protection failure (HPF) 10 Over current du
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-39 Settings 00~65535 This parameter allows the user to enter their password to unloc
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-405.8 Group 7: AC Drive and Motor Parameters 07 - 00 Identity Code of AC Drive Factory Set
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-41 This parameter is used with slip compensation Pr.7-04 to Pr.7-05 and electronic the
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-4207 - 05 Rated Slip Frequency of Motor Factory Setting: 0.00 Settings 0.00~20.00Hz Unit:
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-43 07-11 Reserved Factory setting Setting Range
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-445.9 Group 8: Special Parameters 08 - 00 DC Brake Current Level Factory Setting: 00 Setti
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-45Output frequencyTimeDC Braking TimeONOFFRun/StopDC brakingcurrentlevelDC brakingtime d
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-4608 - 06 Speed Search Time Factory Setting: 0.5 Settings 0.1~5.0 Sec Unit: 0.1 This pa
1 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 1-1CHAPTER 1 RECEIVING AND INSPECTION This VFD-F AC drive has gone through rigorous qual
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-47Master frequency commandOutput frequencyOutput voltageoutput currentSynchronization at
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-48 This parameter determines auto restart time after fault. After fault occurs and restar
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-49 Settings 00: AVR function enabled 01: AVR function disabled 02: AVR function disabled
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-505.10 Group 9: Communication Parameters 09 - 00 Communication Address Factory Setting: 0
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-5109 - 05 Even/Odd Parity and Stopping Parity Setting Factory Setting: 00 Settings 00:
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-5209 - 07 Communication Frequency Setting Factory Setting: 60.00 Settings 0~120.00
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-53 09-10 BACnet DNET Factory Setting 01 Setting Range 01~65535 This parameter d
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-54Present Value X X Status Flag X X Event State X X Out-of-Service X X Units
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-55 Code Description: ASCII mode: Each 8-bit data is the combination of two ASCII charact
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-56 2.2 11-bit character frame (for 8-bit): (8, N, 2: 9-04=1 or 2, 9-05=00) 01234567Start
1 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 1-21.3 Series Number Explanation Production number3055F43AProduction model460V 3-PHASE
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-573. Communication Protocol 3.1 Communication Data Frame: ASCII mode: STX Start charac
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-583.3 CMD (command code) and DATA (data character) The format of data characters depends o
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-59RTU mode: Command message: Response message: Error response message ADR 01H ADR
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-60RTU mode: Command message: Response message: Error response message ADR 01H ADR 01H
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-61RTU mode: Command message: Response message: Error response message ADR 01H ADR
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-62 RTU mode: Command message: Response message: Error response message ADR 01H ADR 01
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-63RTU mode: RTU mode uses CRC (Cyclical Redundancy Check) detect value. CRC (Cyclical Re
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-64The function returns the CRC values as a type of unsigned integer. unsigned int crc_chk(
5 VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-653.5 Address List The contents of available addresses are shown as below: Content Addr
VFD-F Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-66Content Address Function 15: EEPROM WRITE failure (cF1) 16: EEPROM READ failure