VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-54
Present Value X X
Status Flag X X
Event State X X
Out-of-Service X X
Units X
Priority Array X* X*
Relinquish Default X* X*
Active Text X
Inactive Text X
Only with commendable values
VFDF-Analog Values Description
ID Object Name Description Unit
0 AV00:RESERVED software version(.xx) NO_UNITS R
1 AV01:ERROP Error Code(xx.) NO_UNITS R
2 AV02:LEDOP VFDF status(xx.) NO_UNITS R
3 AV03:FSET Frequency Command(xx.xx) HERZ R
4 AV04:FOUT Output Frequency(xx.xx) HERZ R
5 AV05:OUTAMP Output Current(xx.x) AMPERES R
6 AV06:DCBUS DC Bus Voltage(xxx.x) VOLTS R
7 AV07:OUTACV Output Voltage(xxx.x) VOLTS R
8 AV08:PFANGLE PF angle(xx.xx) DEGREE_ANGULAR R
9 AV09:POUT Output Power(xx.xx) KILPWATTS R
10 AV10:PVFB PID feedback physical signal (x.x) NO_UNITS R
11 AV11:SENSOR PID feedback (xx.xx) PERCENT R
12 AV12:USERDL Low part of user define (xx.xx) NO_UNITS R
13 AV13:USERDH High part of user define(xxxx) NO_UNITS R
14 AV14:PLC_TIME PLC time (xxxx) UNIT_SECOND R
15 AV15:TQ_RATIO Torque(xx.x) UNIT_NEWTON_METER R
16 AV16:CMD_REM (RUN/STOP/JOG/FWD/REV) NO_UNITS(resolution 1.0) C
17 AV17:FCMAIN Frequency command HERTZ C
18 AV18:SCMD_REM (EF/Reset/BB) NO_UNITS(resolution 1.0) C
19 AV19:PARAMETERID Parameter ID set 0.0~65535.0 (resolution 1.0) R/W
20 AV20:PARAMETERVALUE Parameter value set 0.0~65535.0 R/W
To set up object AV16 from the BACnet Communication Protocol, Pr02-01 has to be set as 3 or 4.
To set up object AV17 from the BACnet Communication Protocol, Pr02-00 has to be set as 4.
To set up communication parameter from BACnet, please set up the object AV19 then set up
object AV20.
Please refer to the description of Group 00 to set up objects AV00 to AV15.
Please refer to Pr09-06 for the description of object AV16.
Please refer to Pr09-07 for the description of the object AV17.
Please refer to Pr09-08 for the description of the object AV18.
VFDF-Binary Values:
ID Object Name Description Inactive/Active
0 BV00:Ready or Not-Ready Ready State Not Ready/ Ready R
For current Value Access Types, R = Read-only, R/W = Writable, C = Commandable.
Commandable values support priority arrays and relinquish defaults.