VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-80
11 - 04
Motor Switch Delay Time
Factory Setting: 1.0
Settings 0.0~3600.0 sec Unit: 0.1
This parameter determines time interval of two motors during circulative control (11-01=01). Users
need to set suitable time delay to avoid water hammer effect damaging AC drive, motor or system.
This parameter determines time interval between power supply changes from AC drive to
commercial power during fixed circulative control (11-01=02). Users need to set the suitable time
delay to make no shock to motor and runs by commercial power.
11 - 05
Motor Switch Delay Time during Fixed Amount
Circulation
Factory Setting: 10.0
Settings 0.0~3600.0 sec Unit: 0.1
This parameter determines time interval between motor switch frequency and power supply of motor
is not from AC drive during fixed amount circulation (11-01=02)/fixed amount control (11-01=03)
and output frequency of AC drive attained.
As the diagram shown below, after output frequency attains 11-06 motor switch frequency, motor
doesn’t switch at once. It will do motor switch action of circulation control after waiting the delay
time that is set by 11-05. Suitable delay time setting will decrease motor switch times.
After power supply of motor is not from AC drive, the motor will coast to stop according to loading
characteristics. Users need to set 11-06 motor switch frequency and 11-04 delay time of circulation
control according to actual situation to make rotor speed equals to commercial frequency.
11-06
11-08
Commercial power
frequency
Motor 1 frequency
Output frequency of AC drive
01-08
03-00 01
RUN
03-01 02
03-02 03
03-03 04
11-04
11-04
11-05
11-07
11-07