5
VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-87
22 PHL X
23 Lc X
24 FbL X
26 FANP X
27 Fan1 Abnormal X
28 Fan2 Abnormal X
29 Fan3 Abnormal X
30 Fan1,2,3
Abnormal
X
31 Fan1,2 Abnormal X
32 Fan1,3 Abnormal X
33 Fan2,3 Abnormal X
34 FV X X
41 HPF1 X X
42 HPF2 X X
43 HPF3 X X
44 HPF4 X X
45 CF33 X X
46 CF34 X X
47 CF35 X X
48 CF36 X X
49 CF37 X X
50 CF38 X X
11-15 Fire Mode Function
Factory Setting 0
Setting
Range
00 Turn off Fire Mode Function
01 To turn at Clock-wise direction
02 To turn at counter clock-wise direction
This parameter determines to turn on or off the Fire mode function and the direction of fire mode.
11-16 Operation Frequency at Fire Mode
Factory Setting 60.00
Setting
Range
0~FMAX
This parameter determines the operation frequency at fire mode.
11-17
Number of Times to Re-activate while Abnormal
Fire Mode
Factory Setting 0
Setting
Range
0~10
This parameter determines the number of times to re-activate the system while abnormal fire mode.
Able to re-activate while abnormal fire mode: OCOVOHOCCOCAOCNOCDGFF
FV
This parameter is only effective when bypass mode is already set up. If bypass mode is not set up,
then the AC drive will always be reset.