VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-48
This parameter determines auto restart time after fault. After fault occurs and restart, there is no fault
occurs during 08-10 setting time, AC drive will reset fault occurred record to zero.
08 - 11
Operation Frequency Inhibition 1 UP Factory Setting: 0.00
08 - 12
Operation Frequency Inhibition
1 DOWN Factory Setting: 0.00
08 - 13
Operation Frequency Inhibition 2 UP Factory Setting: 0.00
08 - 14
Operation Frequency Inhibition
2 DOWN Factory Setting: 0.00
08 - 15
Operation Frequency Inhibition 3 UP Factory Setting: 0.00
08 - 16
Operation Frequency Inhibition
3 DOWN Factory Setting: 0.00
Settings 0.00~120.00 Hz Unit: 0.01
This parameter determines the inhibition operation frequency range. This function will let AC drive
not run continuous in the resonance frequency of the motor or loading system, or inhibition
operation frequency.
The settings of this parameter should follow as 08-11 08
-12 08 -13 08 -14 08 -15 08 -16.
Master frequency command can be set in inhibition operation frequency range. Now the output
frequency will be limited in the lower bound of inhibition operation frequency.
When AC drive accelerates or decelerates, output frequency will pass through inhibition operation
frequency range.
08 - 17
Automatic Energy-saving
Factory Setting: 00
Settings
00: Energy-saving operation disabled
01: Energy-saving operation enabled
This parameter determines automatic energy-saving function.
70%
Output voltage
100%
Frequency
Automatic Energy-saving Operation
During the auto energy-saving
operation, it will adjust the output
voltage according to the output
power. The maximum output
voltage can be 30% lower than
the normal output voltage.
08 - 18
Automatic Voltage Regulation (AVR)
Factory Setting: 00