5.12 Group 11: Fan and Pump Control Parameters
11 - 00
V/f Curve Selection
Factory Setting: 00
Settings
00: Determined by group 1
01: 1.5 power curve
02: 1.7 power curve
03: 2 power curve
04: cube curve
This parameter is to set V/f curve. If this parameter isn’t set to 00, parameter 01-03 and 01-04 will
disable.
Input current of the motor could divide into two orthogonal vectors: magnetic vector and torque
vector. Gap flux, which is produced by Magnetic vector, is in direct proportion with output voltage
of motor. Torque vector produces torque. Torque is in direct proportion with the result of magnetic
vector multiply by torque vector. In theory, if the value of magnet vector is the same with torque
vector (in unsaturated flux condition), the input current is minimum. If motor loading is unsteady
torque loading (loading torque is in direct proportion with speed. For example, the loading of fan or
pump), loading torque is low during low speed, suitable lower input voltage will decrease input
current of magnetic field to lower flux loss and iron loss of the motor and promote whole efficiency.
When this parameter is set to high power V/f curve and low frequency torque is lower, it is not
suitable for AC drive to accel/decel quickly. If it needs to accel/decel quickly, it is not recommended
to use this parameter.
Frequency
%
02040
60
80
100
10
20
30
40
50
60
70
80
90
100
Voltage%
01-02
01-01
1.5 power curve
1.7 power curve
2 power curve
3 power curve
V/F Curve Diagram