5
VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-23
Setting Functions Descriptions
32 Run PLC Program
33 Pause PLC Program
Parameter value 32 programs Multi-Function Input
Terminal to enable the AC drive internal PLC
program. Parameter value 33 programs an input
terminal to pause the PLC program.
Note: Pr.05-00 to Pr.05-16 defines the PLC
program.
34 Enable source of the second frequency
This terminal allows you to choose the master
frequency or the second one.
35
Enable the source of second operation
command
This terminal allows you to choose the master
operation command or the second one.
36 Motor No.5 output disabled
37 Motor No.6 output disabled
38 Motor No.7 output disabled
39 Motor No.8 output disabled
When multiple motors are controlled by an AC
drive, these settings will allow the corresponding
motor to disable and ignore this motor.
AC drive will not accept the “Motor Output
Disabled signal” when it is running.
40 HOA-Hand mode indication
This terminal enables HOA function.
MI40 ON MI40 OFF
MI41 ON Off mode Auto mode
MI41 OFF
Hand mode
Off mode
41 HOA-Auto mode indication
Pr02-00 Refer to Pr02-00 for the source o
f
frequency
Auto modePr02-14 Refer to Pr02-14 for the source
of frequency. Pr02-15 Refer to Pr02-15 for source o
f
operation command
Off mode: AC Drive is permanently off.
42 (NO) Fire mode (NO)
43 Fire mode (NC)
In accordance with Pr11-15[Fire Mode], this
terminal can start the Fire Mode