5
VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-13
To program this parameter the user must first generate a Hex value with the information above. Then
using the Hex to Decimal conversion to find the corresponding Decimal value and enter it into this
parameter.
For example, a setting of 21 (decimal 21= hex 010101) will display the “H” and “REV” LEDs and
the cursor will stay at the 3rd 7-step display upon power up.
When setting to U LED, please refer to 02-09.
02 - 09
Special Display
Factory Setting: 00
Settings 00: A displays output current of AC drive
01: U displays DC-Bus voltage of AC drive
02: E displays RMS of output voltage
03: P displays feedback signal
04: PLC display auto procedure state
05: T displays heat sink’s temperature
06: The keypad’s screen displays both target value and feedback value
controlled by PID (Proportional–Integral–Derivative controller (PID
controller)).
This parameter chooses the display on the keypad immediately following the “U” user defined
setting.
“MODE” key will scroll from “F”, “H”, “U”, (Pr. 02-09), FWD, and back to “F”.
Users may also use the “LEFT” key on the digital keypad to switch display content.
When Pr02-09 is set to be 6, the keypad’s screen displays both target value and feedback value
controlled by PID as shown below.
Target Value Feedback Value