5
VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-5
01 - 04
Mid-point Voltage Factory Setting: 5.5/11.0
Settings 230V series: 0.1 ~ 255.0V
460V series: 0.2 ~ 510.0V
This parameter sets the Mid-point Voltage of the V/f curve.
This parameter must meet the following argument. Pr.1-02 >= Pr.1-04 >= Pr.1-06.
01 - 05
Minimum Output Frequency Factory Setting: 1.50
Settings 0.10~20.00 Hz
This parameter sets the Minimum Output Frequency of the AC drive. This parameter must be lower
than or equal to the Mid-point frequency
01 - 06
Minimum Output Voltage Factory Setting: 5.5/11.0
Settings 230V series: 0.1 ~ 50.0V
460V series: 0.2 ~100.0V
This parameter sets the Minimum Output Voltage of the AC Drive. The parameter must be lower
than or equal to the Mid-point Voltage.
01 - 07
Upper Bound Frequency Factory Setting: 60.00
Settings 0.00~120.00 Hz
This parameter will limit the maximum output frequency of AC drive. If slip compensation
(Pr.07-02~07-05) or feedback control (Pr.10-00~10-09) are enabled, the output frequency of AC
drive may exceed the Master Frequency Command, but it will continue to be limited by this
parameter setting.
01 - 08
Lower Bound Frequency Factory Setting: 0.00
Settings 0.00~120.00 Hz
This parameter will limit the minimum output frequency. Any Master Frequency Command below
Pr.1-08 will result in an output equal to Pr.1-08.
Upon a start command, the drive will accelerate from Pr.1-05 Minimum Output Frequency to the
Master Frequency Command point.
The Lower Bound Frequency setting must be smaller than the Dwell Frequency (Pr.11-08>=01-08).
If lower bound frequency setting is greater than the Dwell Frequency, the AC drive will equalize the
two settings to the Lower Bound point.