VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-6
Output voltage
Output Frequency
01-02
01-04
01-06
01-00
01-07
01-08
01-0101-05 01-03
01 - 09
Acceleration Time 1
Factory Setting: 10.0/60.0
01 - 10
Deceleration Time 1
Factory Setting: 10.0/60.0
01 - 11
Acceleration Time 2
Factory Setting: 10.0/60.0
01 - 12
Deceleration Time 2
Factory Setting: 10.0/60.0
01 - 13
Acceleration Time 3
Factory Setting: 10.0/60.0
01 - 14
Deceleration Time 3
Factory Setting: 10.0/60.0
01 - 15
Acceleration Time 4
Factory Setting: 10.0/60.0
01 - 16
Deceleration Time 4
Factory Setting: 10.0/60.0
01 - 17
JOG Acceleration Time
Factory Setting: 10.0/60.0
01 - 18 JOG Deceleration Time
Factory Setting: 10.0/60.0
Settings 0.1~3600.0 Sec Unit: 0.1sec
Acceleration time is the time required for the AC drive to ramp from 0 Hz to its Maximum Output
Frequency (Pr.1-00). Deceleration time is the time required for the AC drive to decelerate from
Maximum Output Frequency (Pr.1-00) down to 0 Hz.
An Acceleration or Deceleration time that is too quick, may cause the AC drives protection features
to enable (over-current stall prevention during Accel 06-01 or over-voltage stall prevention 06-00).
If this occurs, the actual Accel/Decel time will be longer than this setting.
Warning: An acceleration or deceleration that is too quick, may cause excess loads on the AC drive
and may permanently damage the drive.
If you want to decelerate the AC drive in short time period, we recommend to add an external brake
module and brake resistor.
You can set 1
st
to 4
th
Accel/Decel time via multi-function input terminals 04-00 to 04-07.