VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-34
5.7 Group 6: Protection Function Parameters
06 - 00
Over-voltage Stall Prevention
Factory Setting: 390.0/780.0
Settings
230V series: 330.0 ~ 410.0VDC
460V series: 660.0 ~820.0VDC
00: Disable
This parameter selects the voltage level for the Over-Voltage Stall Prevention function.
During decelerations, the DC bus voltage may exceed its maximum allowable value due to motor
regeneration. When this function is enabled, the AC drive will stop decelerating and maintain a
constant output frequency. The AC drive will only resume deceleration when the voltage drops
below the preset value.
With moderate inertial loads, the over-voltage stall prevention will not occur and the deceleration
time should be equal to Pr.1-10. With high inertial loads, the AC drive will automatically extend the
deceleration time due to the step function shown below. If the deceleration time is critical for the
application, then dynamic brake resistors should be used.
Output frequency Deceleration characteristic
when Over-voltage stall
prevention enabled
Frequency held
Deceleration Time
Time
06 - 01
Over-current Stall Prevention during Acceleration
Factory Setting: 120
Settings 20~150% Unit: 1
This parameter selects the percentage of allowable over-current during acceleration before the stall
prevention is enabled.
During acceleration, the AC drive output current may increase abruptly and exceed the value
specified by Pr.06-01 due to rapid acceleration or excessive load on the motor. When this function is
enabled, the AC drive will stop accelerating and maintain a constant output frequency. The AC drive
will only resume acceleration when the current drops below the value set in Pr.06-01 (please see the
graph below).
When the over-current stall prevention is activated, the acceleration time of the AC drive will be
longer than the time set in Pr. 01-09.