5.4 Group 3: Output Function Parameters
03 - 00
Multi-function Output terminal 1 (Relay 1)
Factory Setting: 00
03 - 01
Multi-function Output terminal 2 (Relay 2)
Factory Setting: 00
03 - 02
Multi-function Output terminal 3 (Relay 3)
Factory Setting: 00
03 - 03
Multi-function Output terminal 4 (Relay 4)
Factory Setting: 00
03 - 04
Multi-function Output terminal 5 (Relay 5)
Factory Setting: 00
03 - 05
Multi-function Output terminal 6 (Relay 6)
Factory Setting: 00
03 - 06
Multi-function Output terminal 7 (Relay 7)
Factory Setting: 00
03 - 07
Multi-function Output terminal 8 (Relay 8)
Factory Setting: 00
Setting Range 00-43
Setting Functions Descriptions
00 No function
All unused terminals should be set to 00, to assure
they have no effect on derive operation.
01 Motor No. 1
02 Motor No. 2
03 Motor No. 3
04 Motor No. 4
05 Motor No. 5
06 Motor No. 6
07 Motor No. 7
08 Motor No. 8
When starting circulative control, AC drive will
automatic set this parameter by 11-01 ~ 11-03. If
there is only one motor available to operate while
running circulative control, the circulative control
will stop. That means the motor will not be
switched.
09 Auxiliary 1 output
10 Auxiliary 2 output
11 Auxiliary 3 output
12 Auxiliary 4 output
13 Auxiliary 5 output
14 Auxiliary 6 output
15 Auxiliary 7 output
Parameter value 20 to 26 program Multi-Function
Input Terminals (Pr.04-00~Pr.04-07) to correspond
with the AC drive multi-function output terminals
Pr.03-00 to 03-07 (settings 09-15).
16 Indication during operation The corresponding output will be closed during
operation (including DC brake time).
17 Master frequency
attained
The corresponding output will be closed when
output frequency reaches master frequency
command.
18 Zero Speed (including shutdown) The corresponding output will be closed when the
AC drive has no output voltage signal.
19 Over-torque The corresponding output relay will be closed when
the AC drives output current exceeds the
over-torque detection level 06-04.
20 External Fault The corresponding output will be closed when the
EF is enabled. (Pr. 4-00 to 4-07)