
5
VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-85
11 - 11
Stop Frequency of Auxiliary Motor
Factory Setting: 0.00
Settings 0.00~120.00Hz Unit: 0.01Hz
If output frequency of AC drive is less than or equal to this parameter when AC drive is fixed amount
circulation
(11-01=02) or fixed amount (11-01=03), AC drive will make motor stop in sequence.
11-12 Setting of Sleep Mode Function
Factory Setting 00
Setting
Range
01-08
00 Refer to PID Output Command
01 Refer to Feedback signal
When the setting is 00: the Pr11-08 is the <Sleep Frequency of Sleep Process.> while Pr11-09 is the
<Wake Up Frequency of Sleep Process>
When the setting is 01: the Pr11-08 is the Wake Up Feedback Frequency of Sleep Process, while
Pr11-09 is the Sleep Feedback of Sleep Process.>
11-13 Reserved
Factory
Setting
Setting
Range
Reserved
11-14 Delay Time when Switching Circulating Motors (2)
Factory Setting 1.0
Setting
Range
0.0-3600.0 Sec
This parameter determines the delay time of switching circulating motors from mains electricity
while doing fixed amount control (Pr11-01=2)
Kommentare zu diesen Handbüchern