Motor Switch Frequency during Fixed Amount Circulation
Factory Setting: 60.00 Hz
Settings 0.00 to 120.00 Hz Unit: 0.01Hz
This parameter determines frequency that motor runs by commercial power during fixed amount
circulation (11-01=02)/fixed amount control (11-01=03). This parameter should be greater than
commercial frequency. If output frequency of AC drive attains to motor switch frequency, it means
that even motor runs in full speed it can’t make detection value of PID control attains to target value.
Therefore, the power supply of the motor needs to be changed from AC drive to commercial power.
AC drive runs with the next motor and makes the detection value close to target.
In the following chart
T1: enter sleep process time (Pr.11-07)
T2: motor switch delay time during fixed amount circulation (Pr.11-05)
T3: motor switch delay time (Pr.11-04)
N: motor 1
H>(11-06)
H
YES
NO
NO
NO
YES
NO
YES
YES
H<(11-08)
T1=T1+1
T2=T2+1
T1=0
T2=0
NOFF
H0
T2>(11-05)
T1>(11-07)
Fixed amount
circulation
control process
PID control
calculates H
Are there any
motors that
doesn't run?
Are there any
motors that power
supply is from
commercial
power?
Sleep
Process
Fixed amount
circulation switch
process
T1 0
Away from commercial
power in order