2
VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
2-3
2.4 Connections
DANGER
Hazardous Voltage
Before accessing the AC drive:
Disconnect all power to the AC drive.
Wait ten minutes for DC bus capacitors discharge.
Any Electrical or mechanical modification to this equipment without prior written
consent of Delta Electronics, Inc. will void all warranties and may result in a safety
hazard in addition to voiding the UL listing.
Short Circuit Withstand:
The rated voltage of power system that is installed on AC drive must be equal to or less than
240 Volts (460V model is 480 Volts) and the current must be equal to or less than 5000A
RMS.
General Wiring Information
Applicable Codes
All VFD-S AC drives are Underwriters Laboratories, Inc. (UL) and Canadian Underwriters
Laboratories (cUL) listed, and therefore comply with the requirements of the National
Electrical Code (NEC) and the Canadian Electrical Code (CEC).
Installation intended to meet the UL and cUL requirements must follow the instructions
provided in “
Wiring Notes
” as a minimum standard. Follow all local codes that exceed UL
and cUL requirements. Refer to the technical data label affixed to the AC drive and the motor
nameplate for electrical data.
The "Line Fuse Specification" in Appendix B, lists the recommended fuse part number for
each S-Series part number. These fuses (or equivalent) must be used on all installations
where compliance with U.L. standards is a required.