CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS
5.1 Group 0: User Parameters
0 - 00 Identity Code of AC Drive Factory setting: d#
Settings None
1/4 1/2 1 2 3
115V/230V d0 d2 d4 d6 d8
460V -- -- -- d3 d5 d7 d9
This parameter shows the capacity of the AC drive. Users can read Pr.0-01 to check if it
is the rated current of the AC drive corresponds to the identity code shown above and the
current shown below.
1/4 1/2 1 2 3
115V/230V 1.6A 2.5A 4.2A 7.5A 11.0A
460V -- -- -- 1.5 A 2.5 A 4.2 A 5.5 A
0 - 01 Rated Current Display of the AC drive Factory Setting: d ##.#
Settings None Unit: 0.1A
This parameter displays the rated current of the AC drive. It will display based on Pr.0-00,
and is read-only.
0 - 02 Parameter Reset Factory Setting: d 0
Settings d 0 to d 9 Not used
d 10 All parameters are reset to initial factory settings
This setting allows the user to return all parameters to the factory default settings.