1 TPEditor Operation
© DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
1-61
D100 = actual sampling points
D101 = 1
st
point of 1
st
curve
D102 = 1
st
point of 2
nd
curve
D103 = 2
nd
point of 1
st
curve
:
:
and vise versa.
TP series will convert the values into two curves and display them on the screen. (The settings of
Vertical Max and Vertical Min are used to the range of the read registers. If the value exceeds the
range, it will not be displayed on the curve.
Step 3. Click View(V) > Object Inspector command from the menu bar, a Property tab will show up on the
screen and display all the properties of the selected object. The users also could change the settings of
the selected object directly by using the drop-down lists in Property tab.
X-Y Curve
Step 1. After choose Object(O) > X-Y Curve(X) command from the menu bar or click the icon
on the
toolbar to create a X-Y Curve object on the screen. Double-click the selected object by using the mouse,
the following X-Y Curve Setting tab will pop up (Figure 1-107).
Figure 1-107
Step 2. The sampling rule is described as follows:
For example, when the Refer Device is set to D0, TP series will regard the value of D0 as the value of
sampling points and its maximum could be 100 points. The combination of D1 and D2 will become the
first point of X- and Y- axis, the combination of D3 and D4 will become the second point of X- and Y-
axis, … and vise versa. Then, The odd numbers are defined as one group (D1, D3, …) and the even
numbers are defined as another group (D2, D4, …). Then, a X-Y curve could be drawn and displayed
on the screen.
Suppose that Refer Device is D100, then
D100 = actual sampling points