Pr.31
Start-Point for DC Braking Factory Setting: 0.00
Settings 0.00 to 60.00Hz Unit: 0.1sec
This parameter sets the frequency at which the DC Braking will begin during
deceleration.
Master
Frequency
Min. output
Freq.
Pr.29
Pr.31
Pr.30
DC Braking Current %
ON
OFF
Pr.28
Start-point
for DC
braking
Operation
command
time(s)
Notes:
1. DC Braking during starting is used for loads that may move before the AC drive starts,
such as hoists and cranes. These loads may also be moving in the wrong direction. Under
such circumstances, the DC Braking can be used to hold the load in position before
applying a forward motion.
2. DC Braking during stopping is used to stop faster than the ramp-to-stop or to hold a
stopped load in position. A dynamic braking resistor may be needed in order to stop loads
of high inertia.
Pr.32
Momentary Power Loss Operation Selection Factory Setting: 00
Settings 00 Operation stops after momentary power loss
01
Operation continues after momentary power loss Speed search starts
with the Master Frequency reference value
02
Operation continues after momentary power loss Speed search starts
with the min frequency
Pr.33
Maximum Allowable Power Loss Time Factory Setting: 2.0 sec
Settings 0.3 to 5.0 sec Unit: 0.1sec
After a power loss, the AC drive will resume operation only if the power loss duration is
shorter than the time defined by Pr.33. If the Maximum Allowable Power Loss Time is
exceeded, the AC drive output is then turned off.