Pr. 140
External Up/Down Selection
Factory Setting: 00
Settings 00 Fixed Mode (keypad)
01 By Accel or Decel Time
02 Reserved
This parameter is used to change the Master Frequency externally with the Multifuction
Input Terminals. If any two parameters in the group Pr.39-Pr.42 are set to 14 and 15, and
Pr.140 is set to 01, the up/down frequency operation is initiated as the contact closes and
according to the time of acceleration/deceleration.
Pr. 141
Save Frequency Set Point
Factory Setting: 01
Settings 00 Not Save
01 Save
This parameter is used to save the frequency setting before powering off.
Pr. 142
Second Source of Frequency Command
Factory Setting: 00
Settings 00 Keypad Up/Down
01 AVI (0-10V)
02 ACI (4-20mA)
03 RS485
04 Keypad Potentiometer
This parameter changes the source for frequency command by using any Multifunction
Input (Pr.39-Pr.42, setting= 28).
Pr. 143
Software Braking Level
Unit: 0V
Settings 115V/230V series 370 to 450 Vdc Factory setting: 380.0
460V series 740 to 900 Vdc Factory setting: 760.0
575V series 925 to 1075 Vdc Factory setting: 950.0
This parameter sets the level for the dynamic braking to operate. The setting value must
be higher than the steady-state DC BUS Voltage to prevent the braking transistor from
having a 100%-duty. At 100% duty the transistor and resistor will most likely fail.