5
VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-13
J1
V
olta
g
e si
g
nal input
(
0-10V
)
Current si
g
nal input
(
4-20mA
)
! When setting analog overlap plus, it needs to set Pr. 2-06 to select AVI or ACI.
2 - 01 Működési parancs kiadásának forrása Factory Setting: d 0
Settings d 0 Controlled by the keypad
d 1 Controlled by the external terminals, keypad STOP
enabled.
d 2 Controlled by the external terminals, keypad STOP
disabled.
d 3 Controlled by the RS-485 communication interface,
keypad STOP enabled.
d 4 Controlled by the RS-485 communication interface,
keypad STOP disabled.
! When the AC drive is controlled by an external source, please refer to parameter group
4 for detailed explanations on related parameter settings.
2 - 02 Megállásí mód Factory Setting: d 0
Settings d 0 Ramp stop
d 1 Coast stop
! The parameter determines how the motor is stopped when the AC drive receives a valid
stop command.
1. Ramp: the AC drive decelerates the motor to Minimum Output Frequency (Pr.1-05) and
then stops according to the deceleration time set in Pr.1-10 or Pr.1-12.
2. Coast: the AC drive stops output instantly upon command, and the motor free runs until
it comes to a complete stop.