d4, d5 External Faults:
Parameter values d4, d5 programs Multi-Function Input Terminals: M1 (Pr. 4-04), M2 (Pr.
4-05), M3 (Pr. 4-06), M4 (Pr. 4-07) or M5 (Pr. 4-08) to be External Fault (E.F.) inputs.
GND
E.F.(N.O.)
setting by d4
E.F(N.C.)
setting by d5
Mx "Close": Operation available.
Mx "Open":Operation available.
When an External Fault input signal is received, the AC drive will stop all output and display
E.F. on Digital Keypad, the motor will free run. Normal operation can resume after the
External Fault is cleared and the AC drive is reset.
d6 External Reset:
Parameter value d6 programs a Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr.4-05),
M3 (Pr.4-06), M4 (Pr.4-07) or M5 (Pr.4-08) to be an External Reset.
GND
RESET
setting by d6
Mx "Close": Operation available
Note: the External Reset has the same function as the Reset key on the Digital keypad.
After external fault such as O.H., O.C. and O.V. are clear, this input can be used to reset
the drive.
d7, d8, d9 Multi-Step Speed Command:
Parameter values d7, d8, d9 programs any three of the following Multi-Function Input
Terminals: M1 (Pr.4-04), M2 (Pr.4-05), M3 (Pr.4-06), M4 (Pr.4-07) or M5 (Pr.4-08) for
multi-step speed command function.
GND
D7 Multi-step 1
D8 Multi-step 2
D9 Multi-step 3
Mx "Close": Operation available
Mx "Close": Operation available
Mx "Close": Operation available
These three inputs select the multi-step speeds defined by Pr.5-00 to Pr.5-06 as shown in
the following diagram. Pr.5-07 to Pr.5-16 can also control output speed by programming
the AC drives internal PLC function.