VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-46
5.10 Group 9: Communication Parameters
9 - 00 Kommunikációs cím Factory Setting: d 1
Settings d 1 to d254
This parameter can be set during operation.
`
! If the AC drive is controlled by RS-485 serial communication, the communication
address must be set via this parameter.
S1
Computer
S1 S1
RS485
d1
d3
d2
9 - 01 Átviteli sebesség Factory Setting: d 1
Settings d 0 Baud rate 4800 (data transmission speed: bits / second)
d 1 Baud rate 9600 (data transmission speed: bits / second)
d 2 Baud rate 19200 (data transmission speed: bits / second)
d 3 Baud rate 38400 (data transmission speed: bits / second)
This parameter can be set during operation.
! Users can set parameters and control the operation of the AC drive via the RS-485 serial
interface of a personal computer. This parameter is used to set the transmission speed
between the computer and AC drive.
9 - 02 Transmission Fault Treatment Factory Setting: d 0
Settings d 0 Warn and keep operating
d 1 Warn and RAMP to stop
d 2 Warn and COAST to stop
d 3 Keep operation without warning