6. Csoport – VÉDELMI PARAMÉTEREK
Parameters Explanation Settings
Factory
Setting
d0: Tíltva
6-00
Over-Voltage Stall
Prevention
d1: Engedélyezve
d1
230V sorozat: d350 - d410V d390
6-01
Over-Voltage Prevention
Level
460V sorozat: d700 - d820V d780
6-02
Over-Current Stall
Prevention Level
d20 - d150% d130
d0: Disabled
d1: Enabled during constant speed
operation and continue to run to OL1
or OL.
d2: Enabled during Constant Speed
Operation and halted after detection
d3: Enabled during running and continues
before Continuous Output Time Limit
(Pr.6-05) is reached
6-03
Túlnyomaték felismerés
módja
d4: Enabled during running and halted
after Over-Torque detection
d0
6-04
Túlnyomaték felismerés
szintje
d30 - d200% d150
6-05
Túlnyomaték felismerés
idejének beállítása
d0.1 - d10.0 Sec d0.1
6-06
Electronic Thermal
Overload Relay Selection
d0 - d2 d2
6-07
Electronikus hővédelem
karakteriszitikája !
d30 - d600 Sec d60
6-08
Jelenlegi hibakód
d0: Nincs hiba
6-09
Második legjellemzőbb
hiba előhívása
d1: Túláram (oc)
d2: Túlfeszültség (ov)
d3: Túlmelegedés (oH)
6-10
Harmadik legjellemzőbb
hiba előhívása
d4: Túlterhelés (oL)
d0
d5: Túlterhelés (oL1)
d6: Külső hiba (EF)
d7: Nincs használatban
d8: Nincs használatban
d9: Túláram goyrsításkor (ocA)
d10:T
ú
l
á
ram lass
í
t
á
skor (ocd)
d11:Túláram készenléti állapotban (ocn)
d12: Földhiba (GF)