9 - 03 Modbus Communication Watchdog Timer Factory Setting: d 0
Settings d0 Disable Unit: 1 sec
d1 1 sec to d20 20 sec
This parameter can be set during operation.
! If the Watchdog timer function is enabled, the timer will start counting once the first valid
Modbus communication signal is received after power-up or reset. The timer will reset
to 0 after each valid Modbus communication message is received. If the watchdog timer
reaches the value set in Pr. 9-03, the drive will stop its output and display the message
"CE10" on the digital keypad. This fault can reset by an external terminal, keypad or a
Modbus communication reset command.
9 – 04 Kommunikációs protokol Factory Setting: d 0
Settings d 0 Modbus ASCII mode, protocol <7,N,2>
d 1 Modbus ASCII mode, protocol <7,E,1>
d 2 Modbus ASCII mode, protocol <7,O,1>
d 3 Modbus ASCII mode, protocol <8,N,2>
d 4 Modbus ASCII mode, protocol <8,E,1>
d 5 Modbus ASCII mode, protocol <8,O,1>
d 6 Modbus RTU mode, protocol <8,N,2>
d 7 Modbus RTU mode, protocol <8,E,1>
d 8 Modbus RTU mode, protocol <8,O,1>
This parameter can be set during operation.
! 1.Computer Control
6
1
1: +EV
2: GND
3: SG-
4: SG+
# There is a built-in RS-485 serial interface, marked (RJ-11 Jack) on the control
terminal block, for VFD-S Series. The pins are defined above.
Each VFD-S AC drive has a pre-assigned communication address specified by Pr.
(9-00). The computer then controls each AC drive according to its communication
address.
# VFD-S can be setup to communicate on Modbus networks using one of the
following modes: ASCII (American Standard Code for Information Interchange) or
RTU (Remote Terminal Unit). Users can select the desired mode along with the
serial port communication protocol in Pr. 9-04.