VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-44
! Following a power failure, the AC drive will start its speed search operation, only if the
output current is greater than the value determined by Pr.8-07. When the output current
is less than that of Pr.8-07, the AC drive output frequency is at a “speed synchronization
point”. The drive will start to accelerate or decelerate back to the operating frequency at
which it was running prior to the power failure.
Output
Frequency
Output
Voltage
08-06
08-05
08-04=d1
08-06
08-05
08-04=d2
Power
Input
Maximum Allowable
Power Loss Time
Baseblock Time
Speed Search
Speed
Synchronization
Detection
Maximum
Allowable Power
Baseblock Time
Speed search starts
with the Master
Frequency
Speed search starts with
Min. Output Frequency
8 - 08 Skip Frequency 1 Upper Bound Factory Setting: d 0.0
8 - 09 Skip Frequency 1 Lower Bound Factory Setting: d 0.0
8 - 10 Skip Frequency 2 Upper Bound Factory Setting: d 0.0
8 - 11
Skip Frequency 2 Lower Bound
Factory Setting: d 0.0
8 - 12 Skip Frequency 3 Upper Bound Factory Setting: d 0.0
8 - 13 Skip Frequency 3 Lower Bound Factory Setting: d 0.0
Settings d 0.0 to d 400Hz Unit: 0.1Hz
! These parameters determine Skip frequency. It will cause the AC drive to skip operation
at these frequency ranges with continuous frequency output.
! Pr.8-9, Pr.8-11,Pr.8-13 are for Lower Bound setting, and the settings should follow as
Pr.8-9Pr.8-11Pr.8-13.
8 - 14 Hiba utáni autómatikus újraindítás Factory Setting: d 0
Settings d 0 to d 10
! After fault occurs (allowable faults: over-current OC, over-voltage OV), the AC drive can
be reset/restarted automatically up to 10 times. Setting this parameter to 0 will disable the
reset/restart operation after any fault has occurred. When enabled, the AC drive will
restart with speed search, which starts at the Master Frequency.